Cảm biến ngọn lửa và bộ khuếch đại
C7012E1104 Solid State Purple Peeper Ultraviolet Flame Detectors
The C7012A,C,E,F,G Flame Detectors are solid-state electronic devices for sensing the ultraviolet radiation emittedduring combustion of most carbon-containing fuels such as natural gas, LP gas, and oil.
Features:
- Detectors can be mounted horizontally, vertically or at any angle. The self-checking C7012E,F models require faceplate alignment and have integral locating reference points to assure proper shutter mechanism operation.
- Ultraviolet radiation sensing tube and quartz viewing window are field replaceable.
- Threaded conduit fitting and color-coded leadwires allow rapid electrical installation.
- Two flame detectors can be wired in parallel to reduce nuisance shutdowns in difficult flame sighting applications.
- A swivel mount is available to facilitate flame sighting.
- Incorporate UV sensor tube checking feature; used with Honeywell Dynamic Self-Check (R7247C, R7847C)
- Flame Signal Amplifiers.
- Housing meets NEMA 4 enclosure standards (indoor, outdoor protection: rain-tight, dust-tight, hose-directed watertight).
- Protective heat block built into mounting flange.
- High pressure 50 psi (345 kPa) quartz viewing window, focusing lens, swivel mount and antivibration mounting accessories available.
Product Specifications:
- C7012E Self-Checking Solid State Purple Peeper® Ultraviolet Flame Detector: For use with R7247C, and R7847C Dynamic Self-Check Amplifiers.
- Voltage: 12E: Separate models for 100, 120, 208, or 240 Vac, all 50/60 Hz; also models for 110 or 220 volts, 50 Hz only..
- Power Consumption: 7.0 watts maximum
- Operating Temperature: -20°F to 175°F (-29°C to 79°C)
- Storage Temperature Ratings: -60°F to 175°F (-51°C to 79°C).
- Pressure Rating Of Quartz Viewing Window:
- 20 psi (138 kPa). Focusing lens:
- 20 psi (138 kPa) rating or high pressure viewing window
- 50 psi (345 kPa) rating available; see Accessories section
- Mounting flange with either 3/4 or 1 inch NPT internal threads (depending on model) for attaching to sight pipe.
- Wiring Connections:
- NEC Class 1 Color-Coded Leadwires:
- Length: 8 feet (2.4 meters).
- Number of Leadwires: 6.
- NEC Class 1 Color-Coded Leadwires:
- Threaded Leadwire Opening in Faceplate: 1/2-14 NPSM internal threads for attaching conduit.
- Weight: Approximately 4.25 pounds (1.9 kg).
- SIL 3 Capable: The C7012E or F when used with a R7847C self-check amplifier in Relay Module EC7810A, 20A, 30A, 40L, 50A; RM7800[E,G,L,M], 30A, 38[A,B,C], 40[E,G,L,M] 50A, 90[A,B,C,D], 97[A,C], 98A is SIL 3 Capable in a properly designed Safety Instrumented System. See form number 650312 for Certificate Agreement.
- Underwriters Laboratories Inc. Listed (120 Volt Models Only): File no. MP268.
Title | Size | Download |
---|---|---|
Manual C7012A,C,E,F,G Flame Detector | 0.59 MB | Download |