Honeywell
R7800 Series Flame Signal Amplifier Modules
Flame failure response time of 0.8 or 1 second; or 2.0 or 3.0 seconds, depending on the amplifier and relay module selected.
0.0 to 5.0 Vdc Flame signal strength reading range
Tests components 12 times per minute
Feature:
- Flame failure response time of 0.8 or 1 second; or 2.0 or 3.0 seconds, depending on the amplifier and relay module selected.
- 0.0 to 5.0 Vdc Flame signal strength reading range
- Color coded label identifies flame detection type:
- Green-rectification.
- Red-infrared.
- Purple-ultraviolet.
- Blue-pulsed rectification.
- White-optical.
- Tests components 12 times per minute
Technical Information:
- Rectification:
- R7824C for use with C7024E,F Solid State Ultraviolet Detectors.
- R7847A,B for use with flame rods or C7012A,C Solid State Ultraviolet Detectors.
- Infrared:
- R7848A,B for use with C7015 Infrared (lead sulfide) Detector.
- R7852A,B for use with C7915 Infrared (lead sulfide) Detector.
- Ultraviolet:
- R7849A,B for use with C7027/C7035/C7044 Minipeeper Ultraviolet Detectors.
- R7861A for use with C7061A Ultraviolet Detector.
- R7886A for use with C7076A,D Ultraviolet Detectors with adjustable sensitivity.
- Optical:
- R7851B for use with C7927 and C7962 Flame Detectors.
- R7851C for use with C7961E Flame Detectors.
- Flame Signal (Volts dc):
- Minimum Acceptable: 1.25 Vdc.
- Flame Signal Voltage Range (displayed on Keyboard Display Module or measured with a 1M ohm/volt meter plugged into amplifier test jacks): 0.0 to 5.0 Vdc.
- Environmental Ratings:
- Ambient Temperature:
- Operating: -40°F to 140°F (-40°C to 60°C).
- Storage: -40°F to 150°F (-40°C to 65°C).
- Humidity: Operating 85% rh continuous, noncondensing.
- Vibration: Continuous 0.5G environment.
- Ambient Temperature:
- Weight: 2.5 oz (71g), unpacked.
- Dimensions: 91x23x76 mm